Getting Started with Your Fiber Guardian
28 FG-750
Grounding Your Unit
Grounding Your Unit
To avoid the potential for an electrical shock hazard, you must reliably
connect an earth grounding conductor to the unit (AC and DC models).
Note: The DC units are intended for installation with an isolated DC return (DC-I)
and are to be installed in a Common Bonding Network (CBN) per NEBS
GR-1089.
To ground your unit:
1. Remove the two Phillips screws, and remove the grounding lug from
the rear panel of the unit.
2. Prepare the ground wire (minimum 14 AWG), and attach one of its
ends to the unit’s grounding lug using a crimping tool.
3. Use the two Phillips screws to attach the grounding lug and wire
assembly to the rear panel of the unit.
IMPORTANT
Ensure to ground the unit using a grounding method that complies
with your local regulations.
If you are not sure on how to proceed, consult a certified
electrician.